Guide to AKCP Maximum Sensor Cable Length
An outline of the maximum cable length test results with different CAT cable for all AKCP sensors. The AKCP securityProbe and AKCP sensorProbe2+ were used during the test.
Sensor | CAT5 Stranded (in metres) | CAT5E Solid (in metres) | CAT6 Solid (in metres) |
---|---|---|---|
TMP00 | 1000 | 1000 | 1000 |
Thermal Map | 150 | 100 | 150 |
Rope Water | 150 | 150 | 150 |
Locate Water | 100 | 150 | 150 |
Spot Water | 150 | 100 | 150 |
Rope Fuel | 100 | 150 | 150 |
TMP (Wired) | 150 | 100 | 150 |
THS (Wired) | 150 | 150 | 150 |
Airflow | 150 | 100 | 150 |
Dry Contact | 1000 | 1000 | 1000 |
Security Sensor | 1000 | 1000 | 1000 |
Smoke Detector | 100 | 100 | 150 |
4-20mAmp | 100 | 100 | 150 |
Motion Detector | 150 | 150 | 150 |
PRB00-AC | 150 | 150 | 150 |
PRB00-DC | 150 | 100 | 150 |
Siren Strobe | 60 | 20 | 60 |
IODC8 | 500 | 500 | 500 |
Thermocouple | 150 | 150 | 150 |
IDCV | 150 | 150 | 150 |
8-PRB | 150 | 150 | 150 |
5-DCS | 1000 | 1000 | 1000 |
ACV | 1000 | 1000 | 1000 |
Probe Switch [1] | 1000 | 1000 | 1000 |
DCT008 Daisy Chain | 500 | 500 | 500 |
UFLS | 150 | 100 | 150 |
[1] Note: not supported on the sensorProbe2+