Guide to AKCP Temperature Sensors
Jack Hughes
267
A guide to all of the temperature sensors available for your AKCP sensorProbe, sensorProbe+ and securityProbe monitors.
This guide is for comparing the application of the various AKCP temperature and combined temperature & relative humidity sensors. If you wish to integrate more specialist PT100, K type and J type sensors with your AKCP based environment monitoring system, please see the Guide to AKCP Sensor Adaptors for further information.
Sensor | Temperature Range | Temperature Accuracy | Temperature Resolution | Humidity Range | Humidity Accuracy | Humidity Resolution | Length | SKU | Monitor Support | Maximum Cable Length |
---|---|---|---|---|---|---|---|---|---|---|
0.3m Temperature Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | sensorProbe+ series and securityProbe series: ±0.2°C accuracy from -10°C to +75°C sensorProbe series ±1°C accuracy from -10°C to +75°C |
N/A | N/A | N/A | 0.3m | TMP01 | All sensorProbe, sensorProbe+ and securityProbe monitors | Max run length is 300 meters with low capacitance shielded cable or UTP |
1.6m Temperature Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | sensorProbe+ series and securityProbe series: ±0.2°C accuracy from -10°C to +75°C sensorProbe series ±1°C accuracy from -10°C to +75°C |
N/A | N/A | N/A | 1.6m | TMP00 | All sensorProbe, sensorProbe+ and securityProbe monitors | Max run length is 300 meters with low capacitance shielded cable or UTP |
0.3m NIST2 Temperature Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | sensorProbe+ series: ±0.2°C accuracy from -10°C to +75°C | N/A | N/A | N/A | 0.3m | NIST2-T01 | All sensorProbe, sensorProbe+ and securityProbe monitors | Max run length is 300 meters with low capacitance shielded cable or UTP |
1.5m Extendable NIST2 Temperature Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | sensorProbe+ series: ±0.2°C accuracy from -10°C to +75°C | N/A | N/A | N/A | 1.5m (extendable) | NIST2-T00 | All sensorProbe+ monitors | Max run length is 300 meters with low capacitance shielded cable or UTP |
0.3m NIST2 Temperature & Humidity Sensor | -55 to 125°C | sensorProbe+ series: ±0.5°C accuracy from -10°C to +75°C | sensorProbe+ series: 0.1°C increments | 0 to 100% Relative humidity | 1%RH increments, 0.01%RH sensor reading | At 25°C Min: ±2%RH Max: ±5% RH |
0.3m | dTH01 | All sensorProbe+ monitors | Max run length is 300 meters with approved low capacitance shielded cable or UTP |
1.5m NIST2 Extendable Temperature & Humidity Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | sensorProbe+ series: 0.1°C increments | 0 to 100% Relative humidity | 1%RH increments, 0.01%RH sensor reading | At 25°C Min: ±2%RH Max: ±5% RH |
1.5m | dTH00 | All sensorProbe+ monitors | Max run length is 300 meters with approved low capacitance shielded cable or UTP |
4.5m Waterproof Temperature & Humidity Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | sensorProbe+ series 0.1°C increments securityProbe series 0.5ºC increments sensorProbe series 1ºC increments |
0 to 100% Relative humidity | 1%RH increments, 0.01%RH sensor reading | At 25°C Min: ±2%RH Max: ±5% RH |
4.5m Waterproof | THSW15 | All sensorProbe, sensorProbe+ and securityProbe monitors | Max run length is 300 meters with approved low capacitance shielded cable or UTP |
Thermal Map Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | 0.1°C increments | N/A | N/A | N/A | Standard size fits a full height cabinet | TMS | All sensorProbe+ monitors | 18 meters with approved low capacitance shielded UTP cable |
Thermal Map Temperature / Humidity Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | 0.1°C increments | 0 to 100% Relative humidity | 1%RH increments, 0.01%RH sensor reading | At 25°C Min: ±2%RH Max: ±5% RH |
Standard size fits a full height cabinet | THMS | sensorProbe2+ & sensorProbeX monitors | 18 meters with approved low capacitance shielded UTP cable |
Daisy Chain Temperature Sensor | -55 to 125°C | ±0.5°C accuracy from -10 to +75°C | sensorProbe+ series 0.1°C increments securityProbe series 0.5ºC increments sensorProbe series 1ºC increments |
N/A | N/A | N/A | 1.52m extendable | DCT00-X | All securityProbe monitors | Up to 8 DCT sensors per sensor port. Flexible sensor cable length using standard CAT-5E cable (max 152m for the total daisy-chain) |
AKCP 0.3m Calibration Check with Failover Temperature Sensor | -55 to +75°C | ± 0.5°C from -10 to +65°C | sensorProbe+ series 0.1°C increments | N/A | N/A | N/A | 0.3m | TMP01-NIST3 | All sensorProbe+ monitors | 0.3m |
AKCP Ultra Cold Temperature Sensor | -200°C to +150°C | ±0.2°C | sensorProbe+ series 0.1°C increments | N/A | N/A | N/A | 2.07m | UCT15 | All sensorProbe+ monitors | 0.3m |
AKCP 0.3m Calibration Check Dual Temperature & Humidity Sensor | -55 to +75°C | ± 0.5°C from -10 to +65°C | sensorProbe+ series 0.1°C increments | 0 to 100% Relative humidity | 1%RH increments, 0.01%RH sensor reading | At 25°C Min: ±2%RH Max: ±5% RH |
1.5m | THS01-NIST2 | All sensorProbe+ monitors | 0.3m |
AKCP 1.5m Calibration Check Extendable Dual Temperature & Humidity Sensor | -55 to +75°C | ± 0.5°C from -10 to +65°C | sensorProbe+ series 0.1°C increments | 0 to 100% Relative humidity | 1%RH increments, 0.01%RH sensor reading | At 25°C Min: ±2%RH Max: ±5% RH |
1.5m | THS00-NIST2 | All sensorProbe+ monitors | 1.5m extendable up to 40ft on first 4 sensor ports on SPX+ |
AKCP 0.3m Calibration Check with Failover Dual Temperature & Humidity Sensor | -55 to +75°C | ± 0.5°C from -10 to +65°C | sensorProbe+ series 0.1°C increments | 0 to 100% Relative humidity | 1%RH increments, 0.01%RH sensor reading | At 25°C Min: ±2%RH Max: ±5% RH |
1.5m | THS01-NIST3 | All sensorProbe+ monitors | 0.3m |