Changing the Temperature Measurement Units on the Sensatronics EM1

This document explains how to change temperature units in the Sensatronics EM1 Environmental Monitor.

Overview

All Sensatronics EM1 Environmental Monitors come with a built-in webserver. This means that you can view the current readings simply by entering the IP address of the Monitor in your browser. The Index page appears showing details of the Monitor and readings from the various probes attached to the Base Unit.

By default the temperature readings are shown in degrees Fahrenheit, but this can be changed to read in Celsius, Kelvin, or Rankine.

Changing the Temperature Measurement Units

You can reconfigure your EM1 Base Unit.

Connect the serial cable to your PC and to the EM1 base unit.

Run Hyperterminal & connect to the serial port on which you attached the EM1 base unit. The Configuration Main Menu will then be displayed.

A. Set IP Address
B. Set Unit Name & Port Identifiers
C. SNMP, Temp Mode, and Web Settings

R. Reset Unit
X. Restore Default Configuration

Type C and press Return.

The following options appear.

SNMP and Temp Mode Settings Menu

C. Set SNMP Read Community    (Current: public)
D. Set SNMP Write Community    (Current: private)
E. Set SNMP Trap Password         (Current: trap)
S. Enable/Disable SNMP             (Current: Enabled)
F. Set Web Username                (Current: defaultuser)
G. Set Web Password                 (Current: defaultpassword)
I. Set index.html Refresh           (10-65500) (Current: 60s)
U. Toggle Temperature Units      (Units now: Celsius)

R. Return to previous menu

       Enter choice:

Type U.
This switches between the various options. When the required units appear.
Type R.
To return to the Main Menu screen.
To be certain that you have saved the changes, use the Reset option.
Type R to Reset the Base Unit.
The Base Unit will be powered on and off through a full cycle.