Frequencies and Applications

Although it is possible to find just about any cable type used on any network there are some common combinations.

Multimode Applications

Wavelength

Cable size

10M Ethernet 850nm 62.5/125 or 50/125micron
100M Fast Ethernet 1300nm 62.5/125 or 50/125micron
Gigabit Ethernet 850nm/1300nm 62.5/125 or 50/125micron
ATM 155Mbps 1300nm 62.5/125 or 50/125micron
FDDI 1300nm 62.5/125 or 50/125micron
Single Mode Applications Wavelength Cable size
10M Ethernet 1310nm* 8/125micron
100M Fast Ethernet 1310nm* 8/125micron
Gigabit Ethernet 1310*/1550nm 8/125micron
ATM 155Mbps 1310nm* 8/125micron
FDDI 1310nm* 8/125micron

*Note: in practice there is no real difference between 1300nm and 1310nm the different names were used to help differentiate between multimode and single mode systems.

Standards

Cabling needs to conform to ANSI/TIA/EIA-568 Standard for 62.5/125 multimode fibre

ANSI/TIA/EIA-568-B.3 Standard for 50/125 multimode fibre.

The tests you have to do will depend on the Standard you require for your network.

  • TIA/EIA-455-171A FOTP-171 Single ended loss test Standard
  • TIA-526-14-A - OFSTP-14 Double ended loss test Standard
  • TIA-526-7 - OFSTP-7 Single mode cable Standard

Testing details are covered later in this document.

Your rating: None Average: 5 (1 vote)

Comments

Post new comment

By submitting this form, you accept the Mollom privacy policy.